|
DOE/EH-0127 --- Issue No. 90-01 --- 01/89
Copper and Aluminum Cable Connector Problems
BACKGROUND
When preparing to remove old fire alarm notifier circuits to upgrade a fire
alarm notification system, an electrician removed the cover to a junction box
only to discover electrical cable with burned insulation and exposed
conductors. Each of two 500 kcmil aluminum conductors had both their
insulation boot and conductor insulation melted away from their in-line
compression splice. These two exposed phase conductors were within 1/2 inch
of each other. The third phase was intact, with no visible damage to the boot
or the insulation.
Investigation revealed that the two damaged cables had been joined with
compression connectors designed for splicing copper conductors. They were not
listed for use with aluminum cable.
Problems with Aluminum Connectors
The Loss Prevention Guides of the Factory Mutual Engineering Co. describes the
problems with aluminum connectors and offers cost effective preventive
measures.
"...aluminum has the undesirable characteristic of forming a high
resistance film of aluminum oxide on the outside of the conductor when it
is exposed to the air. When the oxide is scraped or wire-brushed off the
conductor, it reforms quickly. Unless the connection is properly prepared,
a high resistance contact is the result and heating is likely to occur."
Aluminum expands 38% more than copper. When terminated with connectors
designed for copper and exposed to load currents, some of the aluminum will be
extruded from the connector. Subsequently, when de-energized, the aluminum
shrinks and oxides form in the voids. The next load cycle experiences
increased resistance in the connection which causes more temperature rise,
more extrusion of the aluminum and higher resistance in the connection. The
sequence repeats itself until the connection fails.
"Creep or cold flow is another factor that has caused heating at the
connections and terminations of aluminum conductors."
"Because aluminum is basically a softer metal than copper, it creeps at
lower pressure."
Aluminum connectors are "...designed with larger contact surfaces to
minimize the pressure (per unit area) exerted on the conductor..."
"Aluminum has a higher creep rate than copper. Consequently, connectors
for aluminum must have more surface area to reduce the pressure on
conductors in a joint."
Corrective Actions:
A complete line of pressure connectors have been designed for making
connections and splices in aluminum conductors of all sizes. However, per DOE
Order 6430.1A, the General Design Criteria, only conductors sized #4 AWG and
larger are permitted to be aluminum. The terminals of power distribution and
utilization equipment must have their terminals identified with the
Underwriters Laboratories, Inc. (UL) designation "AL/CU." This designation
indicates that they are listed by UL as suitable for attaching either copper
or aluminum conductors.
Another factor to consider when joining copper and aluminum where moisture is
present is electrolytic action. A miniature electric cell is created which
eats away the aluminum due to galvanic corrosion. The use of tin-plated
aluminum lugs prevents corrosion.
Although this Safety Note focuses on aluminum conductors classified by UL as
Building Wire and Cable, aluminum conductors may also be found in electric
motors, transformers and other power distribution and utilization equipment.
In a more general scope of concern, increased current flow in electrical
equipment may be due to overloading and insulation breakdown as well as high
resistance connections. Thermal imaging is a fast and efficient method to
detect these problems in their early stages.
Recommendations
As a foundation, the application of aluminum conductors should be controlled
by means of both engineering specifications and approved design, construction,
and maintenance criteria. Then,
- Check all mixed aluminum and copper connections for loosening and
overheating at
least every six months.
- Clean and tighten all electrical connections during each maintenance period
in those
facilities or circumstances where it is impractical to inspect.
An infrared thermal
imaging survey should be made, at least annually, to
detect indications of overheating
so that appropriate corrective action can
be taken.
- Use, in general, the following criteria to determine the condition of connections in fuses,
circuit breakers, knife switches, disconnect and
power switches, cables, bus bars, power
panels, lighting and receptacle
panels, and motor controllers:
- Note 10-15 degrees C (18-27 degrees F) rises above ambient temperature
and plan to reinvestigate within 6 to 12 months.
- When temperature rises are between 15 to 20 degrees C (27 and 36
degrees F) schedule a shutdown for an investigation and possible repair
at a convenient time.
- When the temperature rise is 20 degrees C (36 degrees F) or above, shut
down and investigate immediately.
For additional information and suggestions on this and other related topics,
review the following documents:
Factory Mutual Engineering Corp:
Loss Prevention Data Sheet 5-25 (15-25); "Infrared Thermal Imaging
Systems"
Loss Prevention Data Sheet 5-26 (14-16); "Aluminum Electrical Conductors"
Loss Prevention Data Sheet 5-31 (14-5); "Cables/Bus Bars"
Institute of Electrical and Electronic Engineers:
IEEE Standard 141; "Recommended Practices for Electrical Power
Distribution for Industrial Plants"
This publication is one of several series of bulletins published so that DOE
program managers and contractors can share information about potential
occupational safety problems relevant to DOE operations. For more information
or additional copies, contact Eleanor Crampton, Performance Evaluation
Division, Office of Safety Compliance, Assistant Secretary for Environment,
Safety & Health, U.S. Department of Energy, Washington, DC 20545; telephone
(301)903-3732.
|